This document is a manual of the "open source" program called "OpenSCADA". OpenSCADA represents a SCADA system built on the principles of modularity, multiplatformity and scalability.
As a policy of the development of the program there uses "open source" principle. This choice was done at needs of creation of a free, reliable and publicly available SCADA system. This policy allows to bring together a significant number of developers, enthusiasts and other interested persons to develop, test, improve, distribute and use the program, thus minimizing and distribution of efforts and financial costs.
OpenSCADA is designed for acquisition, archiving, visualization of information, performing of control actions and for other related operations charactered for full-featured SCADA systems. Due to the high level of abstraction and modularization the program can be used in a variety of related industries.
OpenSCADA can be and used now at:
In the role of the common operating system (program platform) for development and using there was selected Linux OS, which is an optimal solution of the following issues:
While the project currently develops under the principles of multiplatformity then there is no most problem for porting the project to other operational systems (program platforms) and hardware platforms. That is planned to future and mostly already done for some platforms.
At the heart of the program is a modular core. And depending on what modules are installed the program can be configured to operate in role of variety servers, clients and both clients and servers in the same time and into the same program. It allows for implementation of the client-server architecture on the same components/modules, saving machine memory, disk space and expensive programming time.
Server configurations of the program were designed for issuing control actions and acquisition, processing, archiving, logging information from different sources and this information providing also to clients (UI, GUI, TUI ...). The modular architecture allows for expanding of server's functionality without it restarting.
Client configurations can be built on different graphics libraries (GUI/TUI ToolKits), as using the program core and its modules (by adding to it an user interface module), or as an independent application connected the OpenSCADA core as a library.
The flexible configuration of the program allows for user to build solutions to meet specific requirements of reliability, functionality and capacity-complexity.
About actual functions and demands of OpenSCADA you can read on the page "Functions and demands" but in this document we will learn the common functions and properties of the program.
In order to achieve flexibility and a high degree of scalability OpenSCADA is constructed in a modular fashion. Tight integration the modules with the core improves the program stability in whole due to repeat of using the well-tuned code. But same process of developing of self code of the modules OpenSCADA imposes greater responsibility — possible errors introduce an element of instability into the program. The ability to create distributed configurations smooths this danger.
OpenSCADA modules are stored within dynamic libraries and each shared library can contain modules of various types. The filling of dynamic libraries by modules is determined by the functional connectivity of the modules itself. Dynamic libraries are hot swappable which allows to update certain parts of the program during the operation. This method of storing of modules' code in dynamic libraries is essential for OpenSCADA, because it is supported by practically all modern operating systems (OS). However, this does not exclude the possibility of developing other methods of storing of the modules' code.
OpenSCADA has the following functional parts implemented in modules:
Management of the modules is carried out by the "Module scheduler" subsystem. The subsystem functions are: connection, switching off, updating and other operations concerned with the modules and their libraries.
Architecturally OpenSCADA is divided into subsystems. Subsystems can be two types: regular and modular. Modular subsystem have the ability of expanding by modules. Each the modular subsystem can contain many of modular objects. For example, the modular subsystem "Databases" contains modular objects of types of databases. Modular object is the root of the module.
Summary OpenSCADA contains nine subsystems with seven being modular. These nine subsystems of OpenSCADA are base ones and their present at every configuration. To the list of these nine subsystems can be added new ones, through the modules themselves. OpenSCADA subsystems:
The subsystem "DAQ" (Data Acquisition) (Fig.1.3) provides to support dynamic data sources whether: PLC, MOD, virtual sources and other. The function of this subsystem is to provide the received data in structured form — the data model and to provide management of these data, for example, these are data modification.
The subsystem "DAQ" is a modular one and it contains modular objects of types of sources of dynamic data. For example, OpenSCADA provides now more than twenty modules and library items by sources of the logical level. Most significant and developed from them are:
Each non-logical source type is implemented into a separate module, which can contain many sources (controller objects), and each source is usually executed in a separate thread-task.
Separately taken object controller may contain parameters specified by module types. For example, the parameters of the analog type, the basic information of which is the value of the integer or the real type. Structurally, the parameter is a list of attributes that contain data. Attributes can have five basic types: logical, integer, real, character string (text) and object. Structures of controller objects, parameters and their types are contained in the subsystem "DAQ" so that the module objects carry out their filling in accordance with their own specifics.
Certain types of data sources themselves can generate data as they generate them entirely, as well as processing physical data, and even fully implement the gathering of these data into OpenSCADA environment and its internal language. Such data sources are called logical. Fully logical data sources are represented by modules: LogicLev and BlockCalc. There are several modules that combine logical data as a result of direct physical ones processing: ModBus, Siemens and OPC-UA.
Dynamic data sources can be remote, that is, they can be generated or received at the remote OpenSCADA station. To communicate with such data sources, the DAQGate gateway module is used. The function of this type of data sources is to display the data sources of the remote OpenSCADA station to the local one.
You can read in detail the key subsystem "DAQ" and its functions in a separate document "Data acquisition in OpenSCADA".
To store data of the program are constantly used databases (DB). In order to unify access and manage databases, OpenSCADA has a subsystem called "Databases" (Fig.1.4). To support different DB/DBMS the subsystem implemented as a modular one.
In the role of modular object contained in the subsystem, the type of DB/DBMS acts, that is, any module of the subsystem "Databases" practically contain the implementation of access to a specific type of database. OpenSCADA provides that most significant and developed modules: SQLite, MySQL, PostgreSQL, FireBird.
Type of the DB/DBMS in its turn contains a list of objects of separate DB of this type, and the database object contains a list of table objects, which contain data in tabular form.
Practically all OpenSCADA data is stored in one or another database. The program's toolkit allows you to easily transfer data from one type of database to another, and, as a result, optimally select a database type for a specific scope of application OpenSCADA. Transferring information from one database to another can be done in two ways. The first one is to change the address of the working DB and to save the whole configuration of the program to it, the second one — it is direct copying information between the database. Except of copying the function of direct editing of content of tables of DB is supported also.
There are two ways to organize the centralized access of a distributed program to a single database. The first is the use of network databases, for example — MySQL. The second way is to use a transport type database on local stations to access one central database of another OpenSCADA station, by sending requests to the database at that remote station — not yet implemented in OpenSCADA.
Data can also be stored in the configuration file of the program. The mechanism of full mapping of the DB structure to the structure of the configuration file is implemented. That is, the standard configuration can be placed in the configuration file. The essence of the mechanism is that the typical (by default) data of programs can be described in the configuration file, for example — when starting without a DB. In the future, these data can be redefined in the DB. In addition, for cases of impossibility to run any DB in general, all data can be stored in the configuration file.
To access databases, a DB registration mechanism is used. Registered DBs in the program are accessible to all OpenSCADA subsystems and can be used in their work. Thanks to this mechanism, you can ensure the distribution of data storage. For example, different libraries can be stored and distributed independently, and connecting a library will be simple registration of the desired DB.
Any SCADA system should provide the ability to archive the gathered data, that is, to form the history of the change (dynamics) of the process. Archives can be divided into two types: messages and values archives.
The peculiarity of message archives is the very archiving of so-called program messages, that is logging. A characteristic sign of a message is the time of its occurrence. Depending on the source the messages can be classified according to different criteria. For example, it can be emergency reports, operator logs, communication failure protocols, and more.
The peculiarity of the value archives is their periodicity, which is determined by the time interval between two adjacent values. Value archives are used to archive the history of continuous processes. Since the process is continuous, it can be archived only by introducing the concept of quantization of the acquired values, otherwise we will receive archives of infinite sizes, in accordance with the continuity of the nature of the process itself. Besides, we can practically get values with a period limited by the data sources themselves. For example, rather high-quality data sources in industry rarely allow data to be received at frequencies above 1 kHz, without taking into account the sensors themselves, which have less qualitative frequency characteristics.
To solve the problems of archiving data streams in OpenSCADA provides a subsystem "Archives-History" (Fig.1.5), which is modular and allows you to maintain archives of messages and values. Modular object, which is contained in the subsystem "Archives-History", is the type of archiver. The type of archiver determines a way of data storing ie the storage — file system, DBMS. Each module of the "Archives-History" subsystem, respectively, can implement the archiving of messages and values, and the subsystem itself can contain many archives that are processed by different modules.
Messages in OpenSCADA are characterized by the date, level of importance, category, and directly the message text. Date of a message indicates the date and time of his creation. Level of importance points to importance of the message. Category defines address or identifier-key of the message source. Often, category contains full path to a source of the message in the program. Text of a message, respectively, has the main meaning of the message.
When archiving messages, they are passed through a filter that works according to importance level and category of messages. Messages level in a filter indicates that you must skip messages with specified or higher levels of importance. For filtering by category, templates or regular expressions are used to determine which messages to pass. Each archiver has its own filter settings, therefore, it is easy to create various specialized archivers for the archive of messages. For example, archivers of messages can be directed to:
There are 8 message levels, but each of these levels, from 1 (first), can be extended by sublevels, ie actually be a group of 10 sublevels by simply adding a number after the basic level, for example, 5 is the basic level and 50...59 is an extension of level 5. Which sets the total number of levels at 80. The seven main levels have names, and correspondence to what is desirable to follow:
In accordance with the nature of messages and violations the subsystem "Archives-History" contains a buffer of current violations, which contains these most actual ones with category of the messages as the key-ID. Access to the buffer-list of current violations is done by indicating the negative value of the message level. Thus, formation of a message with a negative level -2 causes the location of this message in the buffer of active violations with level 2, as well as duplicate it directly in the message archive (the general messages buffer). At forming a message in the same category, but at a positive level — say 1, this violation will be removed from the buffer of violations, and the message will also fall into the message archive (the general messages buffer). Such a mechanism allows simultaneous accounting of active violations and logging of their passage in the message archive. When requesting an archive of messages, the definition of the positive level requests the archive of messages (through the general messages buffer), and the negative to the buffer-list of current violations.
The strict structure of the category and the text of the message is not intended, and the user can create them for their own messages arbitrarily, but account should be taken of the structure of system messages and messages defined by standard OpenSCADA libraries to prevent intersection with them, or targeting expanding:
OpenSCADA values archives act as independent components that include buffers processed by archivers. The main parameter of the values archives is data source, in the role of which may be attributes of the parameters of the subsystem "DAQ", as well as other external data sources (passive mode). Other data sources may be network archivers of remote OpenSCADA stations, OpenSCADA programming environment, and more.
A key component of archiving the values of continuous processes is the value buffer, which is intended for intermediate storing of an array of values obtained with a defined periodicity (time quantum). The values buffer is used to directly store large values of arrays in the value archives both before the direct "flushing" on the physical storage, and for manipulating the value frames, that is, in the functions of the frame-by-frame query of the values and their location in the archive buffer.
To organize remote archivers in distributed configurations, the transport type of archivers is used, which is currently not implemented in OpenSCADA. The function of the transport type of archivers is to display the remote central archiver of OpenSCADA in the local configuration. As a result, the transport-type archiver performs data transfer between the local configuration and the archiver of the remote configuration of the program, by hiding from the subsystems of the local configuration the real nature of the archiver.
Since OpenSCADA is highly scalable, communication support should be sufficiently flexible, for which it is implemented in the "Transports" and "Transport protocols" subsystems (Fig.1.6), which are modular ones.
The "Transports" subsystem is intended to provide for the exchange of unstructured data between OpenSCADA and external systems, in the role of which remote stations OpenSCADA may also serve. Under unstructured data means the stream of characters of a certain length. Modular object contained in the "Transports" subsystem is a type of transport that determines the mechanism for the transmission of unstructured data. For example, their may be and are:
The subsystem "Transports" includes support for input and output transports. Input transports are designed to serve external requests and send replies. Output transports, by contrast, are designed to send messages and wait for a responses. Therefore, input transports contain configuration of local station, as a listening server, and output transports contain configuration of a remote server to connect. That sort of specialization is typical for the "request-response" mechanism, however, currently input and output transports support the independent transmission and reception of data. Modules of the subsystem "Transports" implement support for both input and output transports.
The "Transport protocols" subsystem is designed to structure data received from the "Transports" subsystem, why has the name, is a continuation of the subsystem "Transports" and performs functions of checking structure and integrity of received data. In global notation, this subsystem contains and implements COMMUNICATION protocols! A special configuration field is provided to determine protocol with which transport must operate. Modular object contained in the "Protocols" subsystem is protocol itself. For example, transport protocols can be and are:
The full sequence of incoming communication session for typical "request-response" protocols can be written as follows:
Protocols are also supported for output transports and assume the function of communication with transport and implementation of features of these protocols, when preparing data for the transmission and analysis of responses. The external interface for accessing protocols, from code of other modules and the OpenSCADA programming environment, implements in an XML tree with its own structure for each protocol module. Such a mechanism allows for transparent access to external systems through transports, simply by specifying the name of the protocol by which to serve transmission.
Transports have a possibility to holding additional parameters, whose can be parameters of used protocols, that is protocols can be individually configured to each connection. [PLAN] In further this function will be used for the wrapping protocols.
Thanks to the standard access to transports in OpenSCADA, it's easy to change the way data is exchanged without affecting the exchanging programs themselves. For example, in the case of a local exchange, you can use faster transport based on UNIX-sockets and in the case of exchanging over the Internet and local network use TCP- or UDP-sockets.
SCADA systems, as a class, provide for user interfaces presence. In OpenSCADA for user interfaces, the subsystem "User Interfaces" is provided, which means not only the visualization environment that the end user must work with, but all that is relevant to the user, for example:
The subsystem "User interfaces" is a modular one and its modular object is concrete that user interface itself. Modularity of the subsystem allows you to create different user interfaces in different GUI/TUI libraries and use the most optimal solution in a particular case, for example, you can use Web-based configurators and visualizers (WebCfg, WebCfgD, WebVision, WebUser), and in the case of stationary workstations, use the same configurators and visualizers, but on the basics libraries like Qt (QTCfg, Vision).
OpenSCADA is a ramified program that consists of a dozen subsystems and can include many modules. Therefore, providing all unrestricted access to these resources is least rash. In order to differentiate access, OpenSCADA provides the subsystem "Security" whose main functions are:
OpenSCADA is built on the modular principle, which involves the presence of many modules that need to be controled and scheduled for availability, which is provided for the subsystem "Modules Scheduler". All modules are currently provided to the program through shared libraries (containers) or embedded directly into the OpenSCADA core library according to their logical connection. Each container can contain many different types of modules.
The subsystem "Modules scheduler" controls the state of the containers and allows "hot" plugging, deletion, and updating of the containers and modules it contains.
Obviously, it is impossible to predict all need functions and functions that may be needed in the future so OpenSCADA has the subsystem "Specials" that is modular and designed to provide unpredictable functions through modular extensions. For example, using this subsystem may be implemented:
Modern SCADA system should include mechanisms that enable programming at the user level, that is, the user programming environment. OpenSCADA contains this environment and can be used to:
The programming environment is a set of tools that organize the user's computing area and includes
Modules of function libraries provide static functions of a defined orientation, which extend the object model of the program and represent an user interface for accessing module resources. For example, "Visualization Control Area" can provide functions for issuing various messages, using which the user can implement interactive algorithms for interaction with the program. Function libraries can generally be implemented as a set of fixed-type functions — static ones, and functions that allow free modification and additions — dynamic ones.
Free-style function libraries (dynamic) provide the user-defined writing environment in one of the programming languages; at present, this language is similar to Java implemented by the module DAQ.JavaLikeCalc. In this way you can create libraries of devices of technological processes and many others, and then use them by binding.
On the basis of the functions given by the object model constructs objects of calculating controllers that carry out the binding of functions with the program parameters and the calculation mechanism. Also there construct procedures and protocols of data acquisition of the user level, Widget procedures of "the Visual Control Area" and much more.
SCADA (Supervisory Control And Data Acquisition), in a general view, have the allocated architecture like represented on Figure 2. Elements of SCADA systems, in sense of the software, carry out following functions:
The acquisition server: represents a task or group of tasks engaged in data acquisition from sources of data, or act in a role as a source of data. Into tasks of the server enters:
The server of archiving: represents a task or group of tasks engaged in archiving of data or their history maintenance. Into tasks of the server enters:
The logging server: represents a task or group of tasks engaged in archiving of messages or their history maintenance. Into tasks of the server enters:
The alarm server: represents a task or group of tasks carrying out functions of the server of logging concerning a narrow category of signaling-alarm messages.
The working place of operator: represents constantly functioning GUI (Grafical User Interface) application executed in an one-monitor, multimonitor or panel mode and carrying out functions:
The working place of engineer: represents GUI application used for configuration of SCADA systems. Into tasks of the application enters:
The working place of chief: represents GUI application, executed in an one-monitor mode as a rule, and carrying out functions:
The working place of technologist: completely includes functions of workplace of operator plus models of technological processes (without direct communication with the technological processes).
The working place of technologist-programmer: completely includes functions of workplace of technologist plus a toolkit for creation of models of technological processes.
In the elementary case OpenSCADA can be configured in a server mode (Fig.3.1) for acquisition and archiving of data. The given configuration allows to carry out following functions:
For increasing of reliability and productivity OpenSСADA supposes plural reservation (Fig.3.2) at which data sources (controllers) and archives-history of one copy are reflected in other. At use of a similar configuration there is possible distribution of loading of interrogation/calculation at various stations. The given configuration allows to carry out functions:
Special case of the duplicated connection is the duplicated connection within one server (Fig.3.3), that is starting of several stations at one machine with their parameters crossing. The purpose of the given configuration is increase of reliability and fault tolerance of the configuration by reservation of software.
For visualization of data containing on a server, the good decision is to use the user WEB-interface (Fig.3.4). The given decision allows to use a standard WEB-browser at the client side and therefore is the most flexible as it is not related to one platform, i.e. is multiplatform. However this decision has essential imperfections — that is low productivity and reliability. In this connection it is recommended to use the given method for visualization of noncritical data or data having a reserve highly reliable way of visualization. For example, the good decision will be using of this method in the management of industrial plants where always exists an operator station with a reliable way of visualization. The given configuration allows to carry out following functions:
For visualization of critical data, and also in case of if high quality and productivity is required, it is possible to use visualization on the basis of OpenSCADA configured with a GUI module (Fig.3.5). The given configuration allows to carry out following functions:
The full-function client-server configuration on single machine (Fig.3.6) can be used for increasing of reliability of the configuration as a whole by start of a client and a server in different processes. The given configuration allows, without consequences for the server, to stop the client and to do with it various preventive works. It is recommended for use at stations of the operator by installation of two machines combining in itself a station of the operator and a redundant server. The given configuration allows to carry out following functions:
The mixed connection combines functions of a server and a client (Fig.3.7). It can be used for test, demonstration functions, and also for granting simulators of technological processes as a unit. In this mode following functions can be carried out:
The given configuration is one of variants of robust/reliable connection (Fig.3.8). Stability is reached by distribution of functions on:
The acquisition server is configured on the basis of OpenSCADA and represents a task or a group of data collection tasks — acquisition of a controller or a group of controllers of the same type. Obtained values are available to the central server through any transport which support is added by connecting the corresponding transport module. To reduce the polling frequency and the value of network traffic, the polling server can be equipped with a small archive of values. Configuration of the acquisition server is stored in one of the available databases.
The central server of archiving and maintaining customer requests performs the centralized acquisition and processing of parameters of the polling servers and their values. Access to the polling servers is performed through one of transport + protocols available into OpenSCADA (for example, these Sockets). The module DAQGate is used to provide a single interface for accessing parameters and controllers, which reflects polling server data into the structure of local parameters of data acquisition.
To perform internal computations and additional analysis of parameters, objects of computing controllers are used.
Various archive-history modules are used for versatile and deep archiving.
For access of clients to the server are used accessible for OpenSCADA network transports, for example — Sockets, and transport protocols, for an example — the protocol OpenSCADA "SelfSystem".
The configuration of the central server is stored in one of accessible DB (for example it is network DBMS MySQL).
For granting the user WEB-interface the module WebCfgD by means of the transport protocol "HTTP" is used.
Various clients, including AWPs and WEB clients, are executed on separate machines in the right amount. AWP implements on OpenSCADA basis. Its function is to acquire the values of parameters from the central server and their visualization on the GUI interface(s). To obtain data acquisition parameters the DAQGate remote display parameters module is also used in the AWP. A network-type archive module can be used to provide access to archive-history. The AWP configuration can be stored in one of the available databases (for example, this is a network MySQL database located on the central archiving server machine).
As you can see in the section above, OpenSCADA provides possibility of configuration for execution in different roles. Support for this feature is provided by advanced configuration mechanisms, storage of configuration data and organization of projects of these configurations. This section contains a description of these mechanisms and is intended to give a presentment of flexibility and diversity, thus allowing OpenSCADA to be used for all 100 percent.
When describing the configuration mechanisms and storage methods in this section, emphasis will be placed on the common mechanisms. The specific of configuration and use of modules of OpenSCADA subsystems are provided in their own documentation of these modules.
OpenSCADA uses a declarative approach to describing the configuration interfaces based on the XML language. In fact, specifics of configuration of component of the program are provided by the component itself, thereby running through the entire program, as the nervous system of organism. In terms of OpenSCADA, this is called the OpenSCADA control interface (Control interface). Based on the control interface, graphical user configuring interfaces are created through the use of the OpenSCADA modules. This approach has the following important benefits:
To simplify the configuration process and storing its results, OpenSCADA provides projects of the program which self provide a separate OpenSCADA project folder to save there configuration and all related files. Thus, the OpenSCADA core employs the project selection mechanism, that install working folder and configuration file address according to the specified project. See "OpenSCADA projects" for more details.
OpenSCADA provides three configuration modules on different basis of visualization. Let's observe them and their configuration options:
The configuration can be received in three ways and in the following order: the command line of the program call, the Configuration File and the Data Base. Of which the Configuration File and Data Base are available for change, where the configuration values changed in the configurators are stored.
Typical name of the OpenSCADA configuration file is {sysconfdir}/oscada.xml (where sysconfdir typically is "/etc"), for configurations besides of the OpenSCADA projects, and {Proj}/oscada.xml for the project "Proj". Format of the configuration file and command line parameters we'll examine in the separate section.
Given the modularity of the subsystem "DB", the database may be different. Moreover, it is possible to store different parts of OpenSCADA both in different databases of the same type and in databases of different types.
Many OpenSCADA nodes provide the ability to select a storage to store their data and which can be specified as:
Nodes that do not provide the ability to select a storage work fixedly with the Generic Storage (<gen>), and those that do so also track the availability of their data in different storages and offer a mechanism for sequentially removing duplicates or simply detecting them in different libraries, which are formed by separate databases. You can read more about the mechanisms for transferring the configuration and extracting it to the library in the appropriate "How To".
Changing of some node's configuration will set the modification flag for the node, and also will set to active for buttons "Load from DB", for loading the initial configuration, and "Save to DB" for the changes saving. The modification flag also rises to parent node, which allows to restore-save from the root node, but really into the operations with DB will participate only modified nodes. A node removing causes to removing it from the storage and the modification mechanism does not work for this operation.
Many settings and configurations of the OpenSCADA nodes, which are executed or already enabled, are not applied immediately at changes, because the configuration is read/apply usually only when turn on or start. Therefore to apply the changes, in such cases, it is enough to enable/disable the enabled object or to restart the running one — start/stop. At this time most settings those do not provide direct application are not allowed simply to be edited.
Further examining of configuration of OpenSCADA will be based on the interface of the configurator UI.QTCfg, but the principles of work will be fully consistent with the rest of the configurators owing to the generality in the used control interface of OpenSCADA.
Let's start the observing with configuration of the OpenSCADA system parameters that are placed in the six tabs of the root page of the station:
To modify the fields of this page it may be required the super user's rights. Get these rights you can by means of including your user into the superuser's group "root", or by entering the station from the superuser "root".
We must mention another one important point: the fields of the identifiers of all OpenSCADA objects are unacceptable for direct editing, because they are keys for storage of objects' data inti the database. However, to change the object's identifier you can by the command of cutting and the further pasting of the object (Cut-> Paste) in the configurator.
Service task of the redundancy mechanism is always running and executed at intervals which are prescribed in the appropriate configuration field. Real work on implementing the redundancy is carried out in presence of at least one redundant station in the list of stations, and implies:
It is recommended that the redundancy is configured in such a way that the database of the redundant stations are kept the same, which in the future will allow you to safely copy them, at restoration, to any station and, accordingly, you can save only one set of databases in the backup. In this case, the settings specific to the individual station will be stored in the configuration file and it will be possible to easily configure and change the desired station by choosing the appropriate configuration file.
Redundancy configuration start from the redundant stations appending to the list of OpenSCADA stations in the tab "Subsystem" of the subsystem "Transports" (Fig.4.3b). And to add here you need not only the redundant stations to the current one but the same current one with its external IP, that is some loop. Further this configurations will have been stored into the generic DB of the redundant system, and from this time the DBs will be used in all redundant station creation. Then there is important to make on that stage all needed changes into the generic DB and about this project in general!
Next for the concrete station, with copy of the generic DB, we configure its specific parameters into the tab "Redundancy" of the main page (Fig.4c), which will be stored into the configuration file.
After that all next configurations of the redundancy perform into the tab "Redundancy" of proper subsystem — "Data acquisition" (Fig.4.5b) or "Archives" (Fig.4.6b). If you will set the parameter "Local primary commands transfer" (Fig.4c) then the configurations, like to any other generic ones, can be carried out at one of the stations, and the changes made will fall on all the redundant stations, of course, if they will be available.
For debug of specific of OpenSCADA different working you may be necessary to enable addition-debugging messages generation, which you can set by select minimal messages level, into the tab "Station", to "Debug (0)". As a result of this there will emerge the tab "Debug" (Fig.4e) where available the objects counters for control to leaks, and also the table with categories list of incoming debug messages. Into the table you can select only needed sources of the debug messages and omit to overload the archiving messages subsystem and to decrease significantly for overall performance of the program. You can also to select higher categories, up to root subsystems categories, that will disable the detailed selection and enable all messages generation by the level or by the overall subsystem. For the debug messages observing you need to go subsystem "Archives" (Fig.4.6c), and for this there provided the button "See to messages". The selected debug mode and list of debug categories can be standard stored to the configuration file and on the next boot the debug mode will be activated, this important primarily for the objects counters.
While examining configuration pages of the modular subsystems there will be described general properties of all the modules. However, it should be noted that each module can provide both additional tabs and separate fields for the configuration of its own operation features for pages whose objects are inherited by the modules. Information on the features and additions of the modules can be found in separate documentation for each of them.
This subsystem is the modular one and contains a hierarchy of objects shown in Figure 1.4. To configure the subsystem the root page of the subsystem "DB" containing the tab "Subsystem" and the tab "Modules". The tab "Subsystem" (Fig.4.1a) contains currently only a configuration field for setting the opened tables lifetime, in seconds. The tab "Modules" (Fig.4.1b) is common for all subsystems and contains the list of modules in the subsystem "DB", available at the station.
To modify the page's fields of this subsystem it may be required the super user's rights or the inclusion of your user to the "DB" group.
Each module of the subsystem "DB" provides a configuration page with tabs "DB" and "Module". The tab "DB" (Fig.4.1c) contains a list of database objects registered in the module and a sign of complete removal of database in execution of the deletion command. In the context menu of the database list, the user is given the opportunity to add, remove and switch to the desired database. The tab "Module" contains information about the module of the "DB" subsystem as the each module information fields (Fig.4.1d):
The "DB" subsystem modules contains also a specific information field "Features" with keyword list of supported features:
For the OpenSCADA configuration storing, the storage implementation module must provide at least follow features: GET, SEEK, SET, DEL. And for being the multilanguage storage it must provide also the feature TR.
Each database object contains its own configuration page with the tabs "Data base", "Tables" and "SQL", in case support of SQL-requests. Besides the basic operations you can copy contents of DB by means of the standard function of the objects copying in the configurator. The copying operation of DB contents involves copying of an original database to a destination database, and the contents of the destination database is not cleared before the copy operation. Copying the contents of database is made only when the both databases are enabled, otherwise it will simple copy of the object of the database.
The tab "Data base" (Fig.4.1e) contains the main configuration options of the DB object as follows:
The tab "Tables" (Fig.4.1f) contains a list of opened tables. In normal mode of the program operation this tab is empty, because after completion of working with tables the program closes them. Presence of opened tables tells that the program is now working with the tables or the tables are opened by the user to examine their contents. In context menu of the list of opened tables you can open a table for study (the command "Add"), close an opened table (the command "Delete") and proceed to examination of its contents.
The tab "SQL" (Fig.4.1g) allows only for data bases which support SQL-requests, and contains field to the request enter, button to the request send and table to result. Control of transaction mode of requests provided by a separate configuration field.
Page of examination of contents of tables contains only one the tab "Table". The tab "Table" (Fig.4.1h) contains a field of the name of the table and a table with the contents. The Table of contents provides following functions:
This subsystem is not modular one. To configure the subsystem the root page of the subsystem "Security" is provided, which contains the tab "Users and Groups". This tab "Users and Groups" (Fig.4.2a) contains a list of users and users' groups. Users in the group "Security" or with the rights of the privileged user can add, delete the user or group of users. All other users can go to pages of users or groups of the users and change some personal parameters on the own user page.
For user configuration, a page that contains only the "User" tab (Fig.2.4b) is provided. This tab contains configuration data of the user profile, which can be changed by the user, the user in the "Security" group or the privileged user:
To configure a group of users, a page is provided that contains only the "Group" tab (Fig.4.2c). This tab contains configuration data of the user group profile that can only be changed by the privileged user:
This subsystem is the modular one and contains the hierarchy of objects shown in Figure 1.6. To configure the subsystem it is provided the root page of the subsystem "Transports", containing the tabs "Subsystem" and "Modules".
The tab "Subsystem" (Fig.4.3a) contains a configuration table for external, for this, OpenSCADA stations. External stations may be "System", "User" or both these are selected by the appropriate column. System's external stations are available only to the super user and are used in purpose of components of the system, for example, the horizontal redundancy mechanism and the module DAQ.DAQGate. User's external stations are tied to the user who created them, and thus the list of user's external stations is individual for each user. User's external stations are used by components of the graphical interface, for example, UI.QTCfg, UI.WebCfgD and UI.Vision. In this table of external stations it is possible to add and delete records about the stations, as well as their modification. Each station contains the following fields:
The tab "Modules" (Fig.4.1b) contains a list of modules in the subsystem "Transports" and it is identical for all modular subsystems.
Each module of the subsystem "Transports" provides a configuration page with the tabs "Transports" and "Module".
The tab "Transports" (Fig.4.3b) contains a list of input and output transports registered by the module. Context menu of the transports lists provides the user with the possibility to add, delete and move to the desired transport. The output transports also provide a lifetime function of closing the transports at inactivity. Set it to 0 to disable this function!
On the "Module" tab it is provided the information about the module of subsystem "Transports" (Fig.4.1d), whose structure is identical for all modules.
Each transport contains its own generic configuration dialogues in the tab "Transport" and "Additional". The "Transport" tab contains basic transport settings. Input transport (Fig.4.3c) contains:
Output transport (Fig.4.3d) contains:
The tab "Additional" of both input and output transports contains specific parameters of the transport type and protocols' specific custom parameters. Also there can be reset all the additional parameters to default values and be cleaned the protocols' specific custom parameters.
Output transport, in addition, provides a tab of forming user requests via this transport (Fig.4.3e). The tab is provided for debugging of communications and communication protocols, and includes:
Both input and output transports also contain the tab "IO log" (Fig.4.3f). The tab is provided for generic control, observing and learning the traffic through the transports and includes the log length, block limit, type, aggregation time and the same text area of the log. For the log disable you can the log length field set to zero (0) and -1 for writing to a file.
This subsystem is the modular one. To configure the subsystem the root page of the subsystem "Transport Protocols" is provided, it contains the tab "Modules". The tab "Modules" (Fig.4.1b) contains a list of modules in the subsystem "Transport Protocols" and it is identical for all modular subsystems.
Each module of the subsystem "Transport Protocols" provides the configuration page with the tab "Module". On the tab "Module" there is information on the module of the subsystem "Transport Protocols" (Fig.4.1d), which structure is identical for all modules.
This subsystem is the modular one and contains the hierarchy of objects shown in Figure 1.3. To configure the subsystem the root page of the subsystem "Data acquisition" is provided, which contains the tabs: "Redundancy", "Template libraries" and "Modules".
To obtain access to modify the objects of this subsystem the user of the group "DAQ" or the rights of the privileged user are required.
As a redundancy object of the subsystem "Data Acquisition" there used the controller object for which the redundancy process performs that functions:
The tab "Redundancy" (Fig.4.5a) presented only if at last one station (Fig.4c) pointed into the redundancy and contains the configuration of redundancy of data sources of the subsystem "Data acquisition" with the following settings:
The tab "Template libraries" (Fig.4.5b) contains a list of libraries of templates for the parameters of this subsystem. In the context menu of the list of template libraries the user can add, delete and move to the desired library. The tab "Modules" (Fig.4.1c) contains the list of modules in the subsystem "Transports" and it is identical for all modular subsystems.
Each template library of the subsystem "Data acquisition" provides a configuration page with the tabs "Library" and "Parameter templates". The tab "Library" (Fig.4.5d) contains the basic settings of the library:
The tab "Parameter templates" (Fig.4.5d) contains a list of templates in the library. In the context menu of the list the user can add, delete and go to the desired template.
Each template of the template library provides the configuration page with the tabs "Template" and "IO". The tab "Template" (Fig.4.5e) contains the basic settings of the template:
The tab "IO" (Fig.4.5f) contains the configuration of attributes (Input-Output) of templates and the program text of the template on a language of the user programming of OpenSCADA, for example, "JavaLikeCalc.JavaScript". The sign "Translate program" indicates the preservation and translation of the program text for each language (human) separately, making it difficult to hold the algorithm the same for multilanguage configurations. This feature is generally implemented for compatibility with older versions of OpenSCADA, it is not recommended to install and is currently practicing the translation of specific text messages in the text of the program, through the function tr().
In the table of attributes of template user can, through the context menu: add, insert, delete, move up or down the record of attribute, as well as edit the attribute fields:
The syntax of the language of the template program can be found in the documentation of the module which provides the interpreter of the selected language. For example, a typical user programming language of OpenSCADA is JavaLikeCalc.JavaScript.
Each module of the subsystem "Data acquisition" provides the configuration page with the tabs "Controllers" and "Module". The tab "Controllers" (Fig.4.5g) contains a list of controller objects, registered in the module. In the context menu of the list user can add, delete and move to the desired controller object. On the tab "Module" there is information on the module of the subsystem "Data acquisition" (Fig.4.1d), which structure is identical for all modules.
Each controller object contains its own configuration page with the tabs "Controller", "Parameters" and "Diagnostics".
The tab "Controller" (Fig.4.5h) contains the basic settings. Content of these settings may differ slightly from one module of this subsystem to another, as you can find in the own documentation of the modules. As an example, let's examine the settings of a controller object in the module of the logical level controller DAQ.LogicLev:
The tab "Parameters" (Fig.4.5i) contains a list of parameters in the controller object, provides selection of the type of parameters that are created by default, as well as information on the total number and the number of enabled parameters. In the context menu user can add, delete and go to the desired parameter.
The tab "Diagnostic" (Fig.4.5j) contains diagnostic messages form by the data source. More data sources are external devices with accessing to the data by a network connection or a system bus then there possible different emergency situations on access to the data. Display all their to the field "State" of the controller object impossible due it displays only current access data state. Due the diagnostic you can trace all the emergency situations at view of messages, which forming by the controller object for the specified range of time and by the selected messages level. Besides to certain diagnostic information some modules of the data sources can provide here debug exchange dumps, on the messages level "Debug (0)".
Parameters of the controller objects of the subsystem "Data acquisition" provide a configuration page with the tabs "Parameters", "Attributes", "Archiving", "Inclusion" and "Template configuration".
The tab "Parameter" (Fig.4.5k) contains the main settings:
The tab "Attributes" (Fig.4.5l) contains the parameter attributes and their values in accordance with the configuration of the used template and calculation of its program.
The tab "Archiving" (Fig.4.5m) contains a table with attributes of a parameter in the rows and the archivers in columns. The user can set the archiving for the desired attribute with the required archiver simply by changing the cell at the intersection.
The tab "Inclusion" (Fig.4.5n) contains a list of parameters included hierarchically to other parameter, provides information on the total number and the number of enabled parameters. In the context menu user can add, delete and go to the desired parameter. The parameters inclusion is supported by most the data sources and depth of the inclusion mostly limited 10 levels!
The tab "Template configuration" is't standard, but it is present only in the parameters of modules of the subsystem "Data acquisition", which implement the mechanisms of working under the template in the context of the data source, which they are served, for the logical type. In this review this tab is included for logical completeness of the review of parameter templates configuration of the subsystem "Data acquisition" and as the final stage of of their using. This tab (Fig.4.5o) contains the configuration fields in accordance with the template. In this example it is the group link on the external parameter. This link can be set simply by pointing the way to the parameter, if the flag "Show attributes" is not set, or the attribute addresses separately in the case if the flag is set. Sign "(+)" at the end of the address signals about successful linking and presence of the target.
This subsystem is the modular one and contains the hierarchy of objects shown in Figure 1.5. To configure the subsystem the root page of the subsystem "Archives-History" is provided, which contains the tabs: "Redundancy", "Messages", "Values" and "Modules".
To gain the access to modify the objects of this subsystem the user of the group "Archive" or the privileged user rights are required.
As a redundancy object of the subsystem "Archives-History" there used the object of messages archiver for which the redundancy process performs followed functions:
Redundancy of the values archiving doesn't provided directly but that process does through the data sources and the subsystem of "Data acquisition".
The tab "Redundancy" (Fig.4.6a) presented only if at last one station (Fig.4c) pointed into the redundancy and contains the configuration of redundancy of the messages archiving with the following settings:
The tab "Messages" (Fig.4.6b) contains the configuration of the messages archive and the request form of messages from it.
Configuration of the messages archive is represented by the fields:
The messages request form contains the configuration fields of the request and the table of results. Configuration fields of the request are:
The result table contains rows of messages with the following columns:
For alarm messages, after the table appears a button for clean up this table for the visible alarms, that is useful for service functions. The table also appended for the "Delete" command to remove single alarm.
The tab "Values" (Fig.4.6c) contains the general configuration of the values archiving and list of the value archives. In the context menu of the list of values the user has the opportunity to add, delete and go to the desired archive. The general configuration of the archiving is represented by the fields:
The tab "Modules" (Fig.4.1b) contains the list of modules in the subsystem "Archives-History", available at the station.
The value archive of the subsystem "Archives-History" provides the configuration page with the tabs "Archive", "Archivers" and "Values".
The tab "Archive" (Fig.4.6d) contains the basic settings of the archive:
Tab Archivers' (Fig.4.6e) contains the table with the configuration of the processing of the archive by the available archivers. Lines are available archivers, and the columns are the following parameters:
The tab "Values" (Fig.4.6f) contains the values request in the archive and the result as a table of values or image of the trend. Values request contains the fields:
Each module of the subsystem "Archives-History" provides configuration page with the tabs "Archivers" and "Module". The tab "Archivers" (Fig.4.6g) contains a list of archivers of messages and values registered in the module. The context menu of the list provides the user with possibility to add, delete and go to the desired archiver. On the tab "Module" there is information on the module of the subsystem "Archives-History" (Fig.4.1d), which structure is identical for all modules.
Message archivers contains their own configuration page with the tabs "Archiver" and "Messages".
The "Archiver" tab (Fig.4.6h) contains the basic settings. The structure of these settings may differ slightly from one module to another one of this subsystem as you can find in the own documentation of the modules. As an example we shall examine the settings of the message archiver from the module of the archiving on the file system Arch.FSArch Settings:
The "Messages" tab (Fig.4.6i) contains the form of the messages request from the archive of the archiver:
The result table contains rows of messages with the following columns:
Value archivers contains their own configuration page with the tabs "Archiver" and "Archives".
The "Archivator" tab (Fig.4.6j) contains the basic settings. The structure of these settings may differ slightly from one module to another one of this subsystem as you can find in the own documentation of the modules. As an example we shall examine the settings of the value archiver from the module of the archiving on the file system Arch.FSArch Settings:
The "Archives" tab (Fig.4.6k) contains a table with information about the archives being processed by the archiver. The table in the rows contains the archives, and in the columns — the following information:
In the case of the module Arch.FSArch in this tab you can find the form of exporting the archiver data.
The subsystem is modular one. To configure the subsystem the root page of the subsystem "User Interfaces" is provided, it contains the tab "Subsystem" and the tab "Modules". The tab "Subsystem" (Fig.4.7a) contains currently only a configuration field for setting the syntax highlight font for code. The tab "Modules" (Fig.4.1b) contains a list of modules in the subsystem "User Interfaces" and it is identical for all modular subsystems.
Each module of the subsystem "User Interfaces" provides configuration page with the tabs "User Interface" and "Module". The "User Interface" tab (Fig.4.7b) provides the parameter for monitoring the "Running" status of the module, as well as the configuration sections specialized for the modules of this subsystem. On the "Module" tab it is provided the information about the module of subsystem "User Interfaces" (Fig.4.1d), whose structure is identical for all modules.
Due to the fact that most modules of this subsystem are graphical interfaces, they themselves can provide a developed configuration interface such as the UI.Vision module, and information on the specifics of their configuration can be find in their own documentation of these modules.
The subsystem is modular one. To configure the subsystem the root page of the subsystem "Specials" is provided, it contains the tab "Modules". The tab "Modules" (Fig.4.1b) contains a list of modules in the subsystem "User Interfaces" and it is identical for all modular subsystems.
Each module of the subsystem "Specials" provides configuration page with the tabs "Special" and "Module". The "Special" tab (Fig.4.8) provides the parameter for monitoring the "Running" status of the module, as well as the configuration sections specialized for the modules of this subsystem. On the "Module" tab it is provided the information about the module of subsystem "Specials" (Fig.4.1d), whose structure is identical for all modules.
The subsystem is not modular one. To configure the subsystem "Modules scheduler" the subsystem page is provided, it contains the tab "Subsystem". The "Subsystem" tab (Fig.4.9) contains the basic settings of the subsystem in the contains:
The Configuration File of OpenSCADA is provided to store the generic configuration of OpenSCADA-station. Only in the Configuration File and through the command-line options you can specify a part of the key parameters of the station, so familiarity with the Configuration File structure is necessary for professionals who make peculiar solutions based on OpenSCADA. More information on how to startup and execution OpenSCADA can be found in the section "Startup and execution".
Structure of the Configuration File based on the extensible markup language XML. Correspondingly, strict compliance with XML syntax rules is required. An illustrative example of an OpenSCADA Configuration File with examples of the configuration of most OpenSCADA components is given...
<?xml version='1.0' encoding='UTF-8' ?>
<OpenSCADA>
<!--
This is the OpenSCADA configuration file.
-->
<station id="SimulatorStation">
<!--
Description of the internal parameters of the station.
The station is the OpenSCADA program.
-->
<prm id="StName">AGLKS</prm>
<prm id="WorkDB">SQLite.GenDB</prm>
<prm id="LogTarget">10</prm>
<prm id="LangBase">en_US.UTF-8;uk_UA.UTF-8;ru_RU.UTF-8</prm>
<prm id="SaveAtExit">0</prm>
<prm id="SavePeriod">0</prm>
<node id="sub_BD">
<tbl id="DB">
<fld ID="GenDB" TYPE="SQLite" NAME="Generic DB" NAME_uk="Основна БД" NAME_ru="Основная БД" ADDR="St.db" CODEPAGE="UTF-8" />
</tbl>
</node>
<node id="sub_Security">
<tbl id="Security_user">
<fld NAME="roman" DESCR="Roman Savochenko" PASS="$1$roman$wleNCf/uyA84cGpBn5QuG." />
<fld NAME="root" DESCR="Administrator (superuser)!!!" DESCR_uk="Супер користувач" DESCR_ru="Супер пользователь" PASS="$1$root$lCn57dP9yzkCIAyrwJ24r1" />
<fld NAME="test" DESCR="Test user" PASS="$1$test$pi/xDtU5WFVRqYS6BMU8X/" />
<fld NAME="user" DESCR="Simple user" DESCR_uk="Звичайний користувач" DESCR_ru="Простой пользователь" PASS="$1$user$k8sntSoh7jhsc6lwspjsU." />
</tbl>
<tbl id="Security_grp">
<fld NAME="Archive" DESCR="Archives-History" DESCR_uk="Архіви-Історія" DESCR_ru="Архивы-История" />
<fld NAME="BD" DESCR="Databases" DESCR_uk="Бази даних" DESCR_ru="Базы данных" />
<fld NAME="DAQ" DESCR="Data acquisition" DESCR_uk="Збір даних" DESCR_ru="Сбор данных" />
<fld NAME="ModSched" DESCR="Modules scheduler" DESCR_uk="Диспетчер модулів" DESCR_ru="Диспетчер модулей" />
<fld NAME="Protocol" DESCR="Transport protocols" DESCR_uk="Транспортні протоколи" DESCR_ru="Транспортные протоколы" />
<fld NAME="Security" DESCR="Security" DESCR_uk="Безпека" DESCR_ru="Безопасность" />
<fld NAME="Special" DESCR="Specials" DESCR_uk="Спеціальні" DESCR_ru="Специальные" />
<fld NAME="Transport" DESCR="Transports" DESCR_uk="Транспорти" DESCR_ru="Транспорты" />
<fld NAME="UI" DESCR="User Interfaces" DESCR_uk="Інтерфейси користувача" DESCR_ru="Интерфейсы пользователя" />
<fld NAME="root" DESCR="Administartors group" DESCR_uk="Група адміністраторів" DESCR_ru="Группа администраторов" USERS="roman;" />
<fld NAME="users" DESCR="Users group" DESCR_uk="Група користувачів" DESCR_ru="Группа пользователей" USERS="test;user;" />
<fld NAME="ITW" DESCR="IT worker" DESCR_uk="Робітник IT" DESCR_ru="Работник IT"
LONGDESCR="Information Technology or service worker."
LONGDESCR_uk="Робітник Інформаційних Технологій та сервісу."
LONGDESCR_ru="Работник Информационных Технологий и сервиса." />
<fld NAME="op" DESCR="Operator" DESCR_uk="Оператор" DESCR_ru="Оператор" />
</tbl>
</node>
<node id="sub_ModSched">
<prm id="ModAllow">*</prm>
<prm id="ModDeny" />
<prm id="ChkPer">0</prm>
</node>
<node id="sub_Transport">
<tbl id="ExtTansp">
<fld OP_USER="roman" ID="loop" NAME="Loop" NAME_uk="Петля" NAME_ru="Петля" TRANSP="Sockets" ADDR="TCP:localhost:10005" USER="roman" PASS="roman" />
<fld OP_USER="*" ID="loop" NAME="Loop" NAME_uk="Петля" NAME_ru="Петля" TRANSP="Sockets" ADDR="TCP:localhost:10005" USER="roman" PASS="roman" />
<fld OP_USER="roman" ID="loopSSL" NAME="Loop SSL" NAME_uk="Петля SSL" NAME_ru="Петля SSL" TRANSP="SSL" ADDR="localhost:10045" USER="roman" PASS="roman" />
<fld OP_USER="*" ID="loopSSL" NAME="Loop SSL" NAME_uk="Петля SSL" NAME_ru="Петля SSL" TRANSP="SSL" ADDR="localhost:10045" USER="roman" PASS="roman" />
</tbl>
<tbl id="Transport_in">
<fld ID="Self" MODULE="Sockets" NAME="Self system" DESCRIPT="Main transport of OpenSCADA self protocol."
DESCRIPT_uk="Основний транспорт власного протоколу OpenSCADA." DESCRIPT_ru="Основной транспорт собственного протокола OpenSCADA." ADDR="TCP::10005:1" PROT="SelfSystem" START="1">
<A_PRMS>&lt;prms MaxQueue="10" MaxClients="20" MaxClientsPerHost="5" BufLen="5" KeepAliveReqs="0" KeepAliveTm="60" /&gt;</A_PRMS>
</fld>
<fld ID="WEB_1" MODULE="Sockets" NAME="WEB 1" DESCRIPT="Main transport of the WEB interfaces."
DESCRIPT_uk="Основний транспорт WEB інтерфейсів." DESCRIPT_ru="Основной транспорт WEB интерфейсов." ADDR="TCP::10002:0" PROT="HTTP" START="1">
<A_PRMS>&lt;prms MaxQueue="10" MaxClients="100" MaxClientsPerHost="25" BufLen="5" KeepAliveReqs="0" KeepAliveTm="5" /&gt;</A_PRMS>
</fld>
<fld ID="WEB_2" MODULE="Sockets" NAME="WEB 2" DESCRIPT="Reserve transport of the WEB interfaces."
DESCRIPT_uk="Резервний транспорт WEB інтерфейсів." DESCRIPT_ru="Резервный транспорт WEB интерфейсов." ADDR="TCP::10004:0" PROT="HTTP" START="1">
<A_PRMS>&lt;prms MaxQueue="10" MaxClients="100" MaxClientsPerHost="25" BufLen="5" KeepAliveReqs="0" KeepAliveTm="5" /&gt;</A_PRMS>
</fld>
</tbl>
<!--
<tbl id="Transport_out">
<fld
ID="testModBus"
MODULE="Sockets"
NAME="Test ModBus"
NAME_uk="Тест ModBus"
NAME_ru="Тест ModBus"
DESCRIPT="ModBus protocol exchange test."
DESCRIPT_uk="Тест обміну за протоколом ModBus."
DESCRIPT_ru="Тест обмена по протоколу ModBus."
ADDR="TCP:localhost:10502"
START="1"/>
</tbl>-->
</node>
<node id="sub_DAQ">
<!--
<tbl id="tmplib">
<fld ID="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" DB="tmplib_test2"/>
</tbl>
<tbl id="tmplib_test2">
<fld ID="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR=""
PROGRAM="JavaLikeCalc.JavaScript&#010;cnt=5*i;"/>
</tbl>
<tbl id="tmplib_test2_io">
<fld TMPL_ID="test2" ID="i" NAME="I" NAME_uk="I" NAME_ru="I" TYPE="4" FLAGS="160" VALUE="" POS="0"/>
<fld TMPL_ID="test2" ID="cnt" NAME="Cnt" NAME_uk="Cnt" NAME_ru="Cnt" TYPE="4" FLAGS="32" VALUE="" POS="0"/>
</tbl>-->
<node id="mod_LogicLev">
<!--
<tbl id="DAQ">
<fld
ID="test2"
NAME="Test 2"
NAME_uk="Тест 2"
NAME_ru="Тест 2"
DESCR=""
ENABLE="1"
START="1"
PRM_BD="test2prm"
PERIOD="1000"
PRIOR="0"/>
</tbl>
<tbl id="test2prm">
<fld SHIFR="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR=""
EN="1" MODE="2" PRM="test2.test2"/>
</tbl>-->
</node>
<node id="mod_System">
<!--
<tbl id="DAQ">
<fld
ID="dataOS"
NAME="OS data"
NAME_uk="Дані ОС"
NAME_ru="Даные ОС"
DESCR="Data of services and subsystems of OS."
DESCR_uk="Дані сервісів та підсистем ОС."
DESCR_ru="Данные сервисов и подсистем ОС."
ENABLE="1"
START="1"
AUTO_FILL="0"
PRM_BD="DataOSprm"
PERIOD="1000"
PRIOR="0"/>
</tbl>
<tbl id="DataOSprm">
<fld SHIFR="CPU" NAME="CPU load" NAME_uk="Навантаження CPU" NAME_ru="Нагрузка CPU" DESCR=""
EN="1" TYPE="CPU" SUBT="gen"/>
<fld SHIFR="MEM" NAME="Memory" NAME_uk="Пам'ять" NAME_ru="Память" DESCR="" EN="1" TYPE="MEM"/>
</tbl>
-->
</node>
<node id="mod_DiamondBoards">
<!--
<tbl id="DAQ">
<fld ID="Athena" NAME="Athena board" NAME_uk="Плата Athena" NAME_ru="Плата Athena" DESCR=""
ENABLE="1" START="0" BOARD="25" PRM_BD_A="AthenaAnPrm" PRM_BD_D="AthenaDigPrm" ADDR="640" INT="5"
DIO_CFG="0" ADMODE="0" ADRANGE="0" ADPOLAR="0" ADGAIN="0" ADCONVRATE="1000"/>
</tbl>
<tbl id="AthenaAnPrm">
<fld SHIFR="ai0" NAME="AI 0" NAME_uk="AI 0" NAME_ru="AI 0" DESCR="" EN="0" TYPE="0" CNL="0" GAIN="0"/>
</tbl>
<tbl id="AthenaDigPrm">
<fld SHIFR="di0" NAME="DI 0" NAME_uk="DI 0" NAME_ru="DI 0" DESCR="" EN="0" TYPE="0" PORT="0" CNL="0"/>
</tbl>
-->
</node>
<node id="mod_BlockCalc">
<!--
<tbl id="DAQ">
<fld ID="Model" NAME="Model" NAME_uk="Модель" NAME_ru="Модель" DESCR=""
ENABLE="1" START="1" PRM_BD="Model_prm" BLOCK_SH="Model_blcks" PERIOD="1000" PRIOR="0" PER_DB="0" ITER="1"/>
</tbl>
<tbl id="Model_blcks">
<fld ID="Klap" NAME="Klapan" NAME_uk="Клапан" NAME_ru="Клапан" DESCR=""
FUNC="DAQ.JavaLikeCalc.lib_techApp.klap" EN="1" PROC="1"/>
</tbl>
<tbl id="Model_blcks_io">
<fld BLK_ID="Klap" ID="l_kl1" TLNK="0" LNK="" VAL="50"/>
<fld BLK_ID="Klap" ID="l_kl2" TLNK="0" LNK="" VAL="20"/>
</tbl>
<tbl id="Model_prm">
<fld SHIFR="l_kl" NAME="Klap level" NAME_uk="Положення клапану" NAME_ru="Положение клапана" DESCR=""
EN="1" IO="Klap.l_kl1"/>
</tbl>
-->
</node>
<node id="mod_JavaLikeCalc">
<!--
<tbl id="DAQ">
<fld ID="CalcTest" NAME="Calculation test" NAME_uk="Тест обчислення" NAME_ru="Тест вычисления" DESCR=""
ENABLE="1" START="1" PRM_BD="CalcTest_prm" FUNC="TemplFunc.d_alarm" SCHEDULE="1" PRIOR="0" ITER="1"/>
</tbl>
<tbl id="CalcTest_val">
<fld ID="in" VAL="0"/>
<fld ID="alrm" VAL=""/>
<fld ID="alrm_md" VAL="1"/>
<fld ID="alrm_mess" VAL="Error present."/>
</tbl>
<tbl id="CalcTest_prm">
<fld SHIFR="alrm" NAME="Alarm" NAME_uk="Аварія" NAME_ru="Авария" DESCR="" EN="1" FLD="alrm"/>
</tbl>
<tbl id="lib">
<fld ID="TemplFunc" NAME="" DESCR="" DB="lib_TemplFunc"/>
</tbl>
<tbl id="lib_TemplFunc">
<fld ID="d_alarm" NAME="Digit alarm" NAME_uk="Аварія за дискретним" NAME_ru="Авария по дискретному" DESCR=""
FORMULA="alrm=(in==alrm_md)?&quot;1:&quot;+alrm_mess:&quot;0&quot;;"/>
</tbl>
<tbl id="lib_TemplFunc_io">
<fld F_ID="d_alarm" ID="in" NAME="Input" NAME_uk="Вхід" NAME_ru="Вход" TYPE="3" MODE="0" DEF="" HIDE="0" POS="0"/>
<fld F_ID="d_alarm" ID="alrm" NAME="Alarm" NAME_uk="Аварія" NAME_ru="Авария" TYPE="0" MODE="1" DEF="" HIDE="0" POS="1"/>
<fld F_ID="d_alarm" ID="alrm_md" NAME="Alarm mode" NAME_uk="Режим аварії" NAME_ru="Режим аварии"
TYPE="3" MODE="0" DEF="" HIDE="0" POS="2"/>
<fld F_ID="d_alarm" ID="alrm_mess" NAME="Alarm message" NAME_uk="Повідомлення аварії" NAME_ru="Сообщение аварии"
TYPE="0" MODE="0" DEF="" HIDE="0" POS="3"/>
</tbl>-->
</node>
<node id="mod_Siemens">
<!--
<tbl id="DAQ">
<fld ID="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" ENABLE="1" START="1"
PRM_BD="test2prm" PERIOD="1000" PRIOR="0" CIF_DEV="0" ADDR="5" ASINC_WR="0"/>
</tbl>
<tbl id="test2prm">
<fld SHIFR="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" EN="1" TMPL="S7.ai_man"/>
</tbl>-->
</node>
<node id="mod_SNMP">
<!--
<tbl id="DAQ">
<fld ID="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR=""
ENABLE="1" START="1" PRM_BD="test2prm" PERIOD="1000" PRIOR="0" ADDR="localhost" COMM="public" PATTR_LIM="20"/>
</tbl>
<tbl id="test2prm">
<fld SHIFR="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" EN="1" OID_LS="system"/>
</tbl>-->
</node>
<node id="mod_ModBus">
<!--
<tbl id="DAQ">
<fld ID="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" ENABLE="1" START="1"
PRM_BD="test2prm" PERIOD="1000" PRIOR="0" TRANSP="Sockets" ADDR="exlar.diya.org" NODE="1"/>
</tbl>
<tbl id="test2prm">
<fld SHIFR="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" EN="1"
ATTR_LS="321:0:tst:Test"/>
</tbl>-->
</node>
<node id="mod_DAQGate">
<!--
<tbl id="DAQ">
<fld ID="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" ENABLE="1" START="1"
PRM_BD="test2prm" PERIOD="1000" PRIOR="0" SYNCPER="60" STATIONS="loop" CNTRPRM="System.AutoDA"/>
</tbl>-->
</node>
<node id="mod_DCON">
<!--<tbl id="DAQ">
<fld ID="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" ENABLE="1" START="1"
PRM_BD="test2prm" PERIOD="1" PRIOR="0" ADDR="" REQ_TRY="1"/>
</tbl>
<tbl id="test2prm">
<fld SHIFR="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" EN="1" MOD_TP="0"
MOD_ADDR="1" CRC_CTRL="1"/>
</tbl>-->
</node>
<node id="mod_ICP_DAS">
<!--<tbl id="DAQ">
<fld ID="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" ENABLE="1" START="1"
PRM_BD="test2prm" PERIOD="1" PRIOR="0" BUS="1" BAUD="115200" LP_PRMS="" REQ_TRY="3"/>
</tbl>
<tbl id="test2prm">
<fld SHIFR="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" EN="1"
MOD_TP="552985" MOD_ADDR="0" MOD_SLOT="1" MOD_PRMS="0"/>
</tbl>-->
</node>
<node id="mod_OPC_UA">
<!--<tbl id="DAQ">
<fld ID="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" ENABLE="1" START="1"
PRM_BD="test2prm" SCHEDULE="1" PRIOR="0" SYNCPER="60" ADDR="" EndPoint="opc.tcp://localhost:4841" SecPolicy="None"
SecMessMode="1" Cert="" PvKey="" AttrsLimit="100"/>
</tbl>
<tbl id="test2prm">
<fld SHIFR="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" EN="1" ND_LS=""/>
</tbl>-->
</node>
<node id="mod_SoundCard">
<!--<tbl id="DAQ">
<fld ID="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" ENABLE="1" START="1"
PRM_BD="test2prm" CARD="" SMPL_RATE="8000" SMPL_TYPE="1"/>
</tbl>
<tbl id="test2prm">
<fld SHIFR="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" EN="1" CHANNEL="0"/>
</tbl>-->
</node>
</node>
<node id="sub_Archive">
<prm id="MessBufSize">1000</prm>
<prm id="MessPeriod">5</prm>
<prm id="ValPeriod">1000</prm>
<prm id="ValPriority">10</prm>
<!--
<tbl id="Archive_mess_proc">
<fld
ID="StatErrors"
MODUL="FSArch"
NAME="Errors"
NAME_uk="Помилки"
NAME_ru="Ошибки"
DESCR="Archive of local errors"
DESCR_uk="Архів локальних помилок"
DESCR_ru="Архив локальных ощибок"
START="1"
CATEG="/DemoStation*"
LEVEL="4"
ADDR="ARCHIVES/MESS/stError/"/>
<fld
ID="NetRequsts"
MODUL="FSArch"
NAME="Network requests"
NAME_uk="Мережеві запити"
NAME_ru="Сетевые запросы"
DESCR="Requests to the server via Sockets transport."
DESCR_uk="Запити до сервера через транспорт Sockets."
DESCR_ru="Запросы к серверу через транспорт Sockets."
START="1"
CATEG="/DemoStation/Transport/Sockets*"
LEVEL="1"
ADDR="ARCHIVES/MESS/Net/"/>
</tbl>
<tbl id="Archive_val_proc">
<fld
ID="1h"
MODUL="FSArch"
NAME="1hour"
NAME_uk="1година"
NAME_ru="1час"
DESCR="Averaging at hour"
DESCR_uk="Усереднення за годину"
DESCR_ru="Усреднение за час"
START="1"
ADDR="ARCHIVES/VAL/1h/"
V_PER="360"
A_PER="60"/>
</tbl>
<tbl id="Archive_val">
<fld
ID="test1"
NAME="Test 1"
NAME_uk="Тест 1"
NAME_ru="Тест 1"
DESCR="Test 1"
DESCR_uk="Тест 1"
DESCR_ru="Тест 1"
START="1"
VTYPE="1"
BPER="1"
BSIZE="200"
BHGRD="1"
BHRES="0"
SrcMode="0"
Source=""
ArchS=""/>
</tbl>-->
</node>
<node id="sub_Protocol">
</node>
<node id="sub_UI">
<node id="mod_QTStarter">
<prm id="StartMod">QTCfg</prm>
<prm id="CloseToTray">0</prm>
<prm id="Style"></prm>
<prm id="Palette"></prm>
<prm id="StyleSheets"></prm>
<tbl id="LookFeel">
<fld NAME="Typical TDE" STYLE="" STL_SHTS="">
<PALETTE>#000000, #dddfe4, #ffffff, #ffffff, #555555, #c7c7c7, #000000, #ffffff, #000000, #ffffff, #efefef, #000000, #678db2, #ffffff, #0000ee, #52188b
#808080, #dddfe4, #ffffff, #ffffff, #555555, #c7c7c7, #c7c7c7, #ffffff, #808080, #ffffff, #efefef, #000000, #567594, #ffffff, #0000ee, #52188b
#000000, #dddfe4, #ffffff, #ffffff, #555555, #c7c7c7, #000000, #ffffff, #000000, #ffffff, #efefef, #000000, #678db2, #ffffff, #0000ee, #52188b</PALETTE>
</fld>
<fld NAME="Blue Slate" STYLE="" STL_SHTS="">
<PALETTE>#000000, #9db9c8, #f6fcff, #c9dae3, #4e5c64, #697b85, #000000, #bfe2f4, #000000, #c3c3c3, #9db9c8, #000000, #558097, #ffffff, #0000ee, #52188b, #b4b4b4, #000000, #ffffdc, #000000
#808080, #9db9c8, #f6fcff, #b5d5e6, #4e5c64, #697b85, #808080, #bfe2f4, #808080, #c3c3c3, #9db9c8, #000000, #558097, #808080, #0000ee, #52188b, #b4b4b4, #000000, #ffffdc, #000000
#000000, #9db9c8, #f6fcff, #b5d5e6, #4e5c64, #697b85, #000000, #bfe2f4, #000000, #c3c3c3, #9db9c8, #000000, #558097, #ffffff, #0000ee, #52188b, #b4b4b4, #000000, #ffffdc, #000000</PALETTE>
</fld>
<fld NAME="Blue Darkness" STYLE="" STL_SHTS="">
<PALETTE>#ffffff, #426794, #5788c3, #4871a2, #162231, #37567b, #dcdcdc, #5788c3, #ffffff, #002a4e, #426794, #000000, #5cb3ff, #000000, #00ffff, #c0c0ff
#555555, #426794, #5788c3, #4871a2, #162231, #37567b, #37567b, #5788c3, #555555, #002a4e, #426794, #000000, #4c95d4, #ffffff, #00ffff, #c0c0ff
#ffffff, #426794, #5788c3, #4871a2, #162231, #37567b, #dcdcdc, #5788c3, #ffffff, #002a4e, #426794, #000000, #5cb3ff, #000000, #00ffff, #c0c0ff</PALETTE>
</fld>
</tbl>
</node>
<node id="mod_QTCfg">
<prm id="StartUser">roman</prm>
</node>
<node id="mod_Vision">
<prm id="StartUser">roman</prm>
</node>
<node id="mod_WebCfg">
<prm id="SessTimeLife">20</prm>
</node>
<node id="mod_VCAEngine">
<!--
<tbl id="LIB">
<fld ID="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR=""
DB_TBL="wlib_test2" ICO="" USER="root" GRP="UI" PERMIT="436"/>
</tbl>
<tbl id="wlib_test2">
<fld ID="test2" ICO="" PARENT="/wlb_originals/wdg_Box" PROC="" PROC_PER="-1"
USER="root" GRP="UI" PERMIT="436"/>
</tbl>
<tbl id="wlib_test2_io">
<fld IDW="test2" ID="name" IO_VAL="Test 2" IO_VAL_uk="Тест 2" IO_VAL_ru="Тест 2" SELF_FLG="" CFG_TMPL="" CFG_VAL=""/>
<fld IDW="test2" ID="dscr" IO_VAL="Test of the module 2" IO_VAL_uk="Тест модуля 2" IO_VAL_ru="Тест модуля 2" SELF_FLG="" CFG_TMPL="" CFG_VAL=""/>
</tbl>
<tbl id="PRJ">
<fld ID="test2" NAME="Test 2" NAME_uk="Тест 2" NAME_ru="Тест 2" DESCR="" DB_TBL="prj_test2" ICO="" USER="root" GRP="UI" PERMIT="436"/>
</tbl>
<tbl id="prj_test2">
<fld OWNER="/test2" ID="pg1" ICO="" PARENT="/wlb_originals/wdg_Box" PROC="" PROC_PER="-1" USER="root" GRP="UI" PERMIT="436" FLGS="1"/>
<fld OWNER="/test2/pg1" ID="pg2" ICO="" PARENT="/wlb_originals/wdg_Box" PROC="" PROC_PER="-1" USER="root" GRP="UI" PERMIT="436" FLGS="0"/>
</tbl>
<tbl id="prj_test2_incl">
<fld IDW="/prj_test2/pg_pg1" ID="wdg1" PARENT="/wlb_originals/wdg_Box"/>
</tbl>-->
</node>
</node>
<node id="sub_Special">
<node id="mod_SystemTests">
<prm id="Param" on="0" per="5" name="LogicLev.experiment.F3" />
<prm id="XML" on="0" per="10" file="/etc/oscada.xml" />
<prm id="Mess" on="0" per="10" arhtor="DBArch.test3" depth="10" />
<prm id="SOAttach" on="0" per="20" name="../../lib/openscada/daq_LogicLev.so" mode="0" full="1" />
<prm id="Val" on="0" per="1" name="LogicLev.experiment.F3.var" arch_len="5" arch_per="1000000" />
<prm id="Val" on="0" per="1" name="System.AutoDA.CPULoad.load" arch_len="10" arch_per="1000000" />
<prm id="DB" on="0" per="10" type="MySQL" addr="server.diya.org;roman;123456;oscadaTest" table="test" size="1000" />
<prm id="DB" on="0" per="10" type="DBF" addr="./DATA/DBF" table="test.dbf" size="1000" />
<prm id="DB" on="0" per="10" type="SQLite" addr="./DATA/test.db" table="test" size="1000" />
<prm id="DB" on="0" per="10" type="FireBird" addr="server.diya.org:/var/tmp/test.fdb;roman;123456" table="test" size="1000" />
<prm id="TrOut" on="0" per="1" addr="TCP:127.0.0.1:10001" type="Sockets" req="time" />
<prm id="TrOut" on="0" per="1" addr="UDP:127.0.0.1:10001" type="Sockets" req="time" />
<prm id="TrOut" on="0" per="1" addr="UNIX:./oscada" type="Sockets" req="time" />
<prm id="TrOut" on="0" per="1" addr="UDP:127.0.0.1:daytime" type="Sockets" req="time" />
<prm id="SysContrLang" on="0" per="10" path="/Archive/FSArch/mess_StatErrors/%2fprm%2fst" />
<prm id="ValBuf" on="0" per="5" />
<prm id="Archive" on="0" per="30" arch="test1" period="1000000" />
<prm id="Base64Code" on="0" per="10" />
</node>
</node>
</station>
</OpenSCADA>
Let's examine the structure of the configuration file in detail. One configuration file can contain the configuration of several stations in the sections <station id="SimulatorStation"/>. The "id" attribute specifies the station identifier — class of the station. Use of this or that section of the station is indicated by the command line parameter --station=SimulatorStation when starting. The section of the station directly contains station parameters and subsystem sections. Section configuration parameters are written as <prm id="StName">AGLKS</prm> , where the "id" attribute specifies the parameter ID, and in the body of the "prm" tag, the value "AGLKS" for the parameter is specified. The list of available parameters and their description for the station and all other sections can be obtained from the console by starting OpenSCADA with the parameter --help.
The subsystem sections <node id="sub_DAQ" /> contain: subsystem parameters, module sections, and table sections for reflections of the data of databases in the configuration file. Module sections <node id="mod_DiamondBoards" /> contain individual module parameters and table sections for reflections of the data of databases in the configuration file.
The sections of the tables of reflection of the data of databases are provided for placement in the configuration file records of DB tables for the OpenSCADA components. Let's examine the table of the input transports "Transport_in" of the subsystem "Transports" <node id="sub_Transport"> from the above provided example of the configuration file. The table contains three records with the fields: ID, MODULE, NAME, DESCRIPT, ADDR, PROT, START. After starting with this section and in general without the DB in the subsystem "Transports" of the module "Sockets" you'll see three input transports. The formats of the table structures of the main components are included into the demo configuration file — models of technological processes. For details of the structure of the database tables refer to the documentation of the corresponding modules or simply save the desired object to the configuration file.
The result of the command execution openscada_AGLKS --help ...
*************************************************************************** ********** OpenSCADA v0.9+r2535 (Linux-4.9.0-0.bpo.5-amd64). ********* *************************************************************************** =========================================================================== ==================== Generic options ====================================== =========================================================================== -h, --help This help text about the program command-line options and configuration file parameters. --projName=<name> OpenSCADA project name to switch it. For this feature there also uses an environment variable "OSCADA_ProjName" and the program binary name "openscada_{ProjName}". --projUserDir={dir} Directory of user projects (writeable) of OpenSCADA, "~/.openscada" by default. --projLock={per} Uses the projects locking by creation the \"lock\" file in the project folder and update it in the period <per>, by default it is enabled and the updating period <per> is 60 seconds. To disable set the updating period <per> to zero. --lang=<LANG> Station language, in the view "en_US.UTF-8". --config=<file> Station configuration file. --station=<id> Station identifier. --statName=<name> Station name. --modDir=<path> Directories with the modules, separated by ';', they can include a files' template at the end. --messLev=<level> Level of the processing messages (0-7). --log=<direct> Direct messages to, by the bitfield: 0x1 - syslogd; 0x2 - stdout; 0x4 - stderr; 0x8 - the messages archive. --consoleCharSet={CharSet} Forcing to the console <CharSet> for the console messages, by default it is system one. --demon, --daemon Run in the daemon mode. --pidFile=<file> File for the program process ID placing here. --noCoreDump Prevents from the core dump creation at crashes - don't set the limit to the unlimited value. --permCrtFiles={perm} Permissions of the created OpenSCADA files, by default it is 0755 (RWXRW_RW_). ----------- Station 'AGLKS(SimulatorStation)' settings in the configuration file ----------- StName <nm> Station name. WorkDB <Type.Name> Working DB (<type> and <name>). WorkDir <path> Working directory. ModDir <path> Directories with the modules, separated by ';', they can include a files' template at the end. IcoDir <path> Icons directory. DocDir <path> Documents directory. MessLev <level> Level of the processing messages (0-7). SelDebCats <list> Debug categories list, separated by ';'. LogTarget <direction> Direct messages to, by the bitfield: 0x1 - syslogd; 0x2 - stdout; 0x4 - stderr; 0x8 - the messages archive. Lang <lang> Station language-locale in the view "en_US.UTF-8". LangBase <lang> Base language and the project whole locales (like to "en_US.UTF-8") list (optional) separated by ';', for the multilanguage mode. MainCPUs <list> Main list of the using CPUs, separated by ':'. TaskInvPhs <n> Number of phases of the task invoking, 1 to disable the phasing. ClockRT <0|1> Sets the clock source to use to REALTIME (otherwise MONOTONIC), which is problematic one at the system clock modification. SaveAtExit <0|1> Save the program at exit. SavePeriod <seconds> Period of the program saving, 0 to disable. ModifCalc <0|1> Set modification for the calculated objects. RdStLevel <lev> Level of the redundancy of the current station. RdTaskPer <seconds> Call period of the redundancy task. RdRestConnTm <seconds> Time to restore connection to "dead" reserve station. RdStList <list> Redundant stations list, separated symbol ';' (st1;st2). RdPrimCmdTr <0|1> Enables the transmission of primary commands to the reserve stations. Global configurable limits: limObjID_SZ [*20..50] ID size of the OpenSCADA objects. WARNING! Big size can cause the key limit error on MySQL like DB! Change that once before use on DBs with the fixed type "char({N})"! limObjNm_SZ [*100...200] NAME size of the OpenSCADA objects. WARNING! Change that once before use on DBs with the fixed type "char({N})"! limArchID_SZ [*50...90] ID size of the value archive objects. WARNING! Increase it only, else you can get problems on Archive.FSArch! Change that once before use on DBs with the fixed type "char({N})"! limUserFile_SZ [1MB...*10MB...1000MB] The files size limit at loading and processing in the userspace and the part size of the big files transferring. limUserIts_N [1000...*1000000...1000000000] The limit on count of creating user items, like to array items. limCacheIts_N [*100...100000] The limit on count of the caching items. limCacheIts_TM [10...*60...1000] The limit on the caching items time, seconds. Global configurable parameters: prmStrBuf_SZ [1000...*10000...1000000] Length of string buffers, no string class. prmWait_DL [0.001...*0.1...1] Quantum of the waiting time cycles, seconds. prmWait_TM [*5...10] Standard waiting timeout length, seconds. prmInterf_TM [*7...15] Time of waiting for the interface reaction, seconds. prmServTask_PER [1...*10...120] Service task period, seconds. ========================= Subsystem "DB" options ======================== ------ Parameters of the section '/sub_BD/' of the configuration file ------ TblLifeTime <seconds> Opened tables lifetime (by default 600 seconds). ======================= Subsystem "Security" options ==================== ======================= Subsystem "Transports" options ================== ======================= Module <Transport:Sockets> options ======================= ---- Parameters of the module section '/sub_Transport/mod_Sockets/' of the configuration file ---- OutLifeTime <seconds> Output transports lifetime (by default 0 seconds), 0 to disable the function. ======================= Module <Transport:Serial> options ======================= ---- Parameters of the module section '/sub_Transport/mod_Serial/' of the configuration file ---- OutLifeTime <seconds> Output transports lifetime (by default 0 seconds), 0 to disable the function. ======================= Module <Transport:SSL> options ======================= ---- Parameters of the module section '/sub_Transport/mod_SSL/' of the configuration file ---- OutLifeTime <seconds> Output transports lifetime (by default 0 seconds), 0 to disable the function. =============== Subsystem "Transport Protocols" options ================= ======================= Module <Protocol:HTTP> options ======================= ---- Parameters of the module section '/sub_Protocol/mod_HTTP/' of the configuration file ---- AuthTime <min> Life time of the authentication session, in minutes (default 10). =================== Subsystem "Data acquisition" options ================ ------ Parameters of the section '/sub_DAQ/' of the configuration file ------ RdRestDtTm <hour> Depth of recovery time of archive data from the reserve station, when startup, in hours. ======================== Subsystem "Archives-History" options =================== ------ Parameters of the section '/sub_Archive/' of the configuration file ------ MessBufSize <items> Size of the messages buffer. MessPeriod <seconds> Period of the messages archiving. ClrAlrmDays <days> Days of the alarms automatic clearing. ValPeriod <mseconds> Period of active archiving of values. ValPriority <level> Level of priority of the task of active archiving of values. RdRestDtOverTm <days> Depth of the forced overloading of the reserve history at startup, in days. ======================= Module <Archive:FSArch> options ======================= --noArchLimit Disable the limit on number of files. Use for archive the viewing mode, not for work. ======================= Subsystem "Specials" options ===================== ======================= Module <Special:SystemTests> options ======================= ---- Parameters of the module section '/sub_Special/mod_SystemTests/' of the configuration file ---- *** Main options of all the tests *** id test id; on flag enabling test; per period of repeating, seconds. *** Test options *** 1) Param DAQ test parameters. Reads the attributes and configuration fields of the parameter. 1:name DAQ parameter address 2) XML XML parsing file test. Disassembles and displays the structure of the specified file. 1:file XML file 3) Mess Test the archive of messages. Periodically reads new messages from the archive for the specified archiver. 1:arhtor Archiver 2:categ Message category template 3:depth Messages depth, seconds 4) SOAttach Test attach/detach module. 1:name Path to the module 2:mode Mode (1-attach;-1-detach;0-change) 3:full Complete attach(startup) 5) Val Test the attribute value of the parameter. Performs a periodic acquisition of the last value of the specified attribute, as well as the archive questioning to the required depth. 1:name Path to the parameter attribute 2:arch_len Depth of getting of archive values, seconds 3:arch_per Depth of getting of archive values, microseconds 6) DB Full database test. Make: - make/open DB; - make/open table; - make multiply records for the determined structure; - modify multiply records; - get and check values for multiply records; - modify a record and the table structure; - remove multiply records; - close/remove table; - close/remove DB. 1:type DB type 2:addr DB address 3:table DB table 4:size Records number 7) TrOut Test of the output and/or input transport. Performs testing of the original transport by sending a request to the specified input transport. 1:addr Address 2:type Transport module 3:req Text of the request 8) SysContrLang The test of the control language of the program. Performs query of language elements through a complete path. The full path to the language element looks like </Archive/%2fbd%2fm_per>. The complete path consists of two nested paths. The first </Archive/> is the path to the node of the control tree. The second </bd/m_per> is the path to the specific node element. 1:path Path to the language element 9) ValBuf The tests of the values buffer. Contains 13 tests of all aspects of the value buffer (the subsystem "Archives"). 10) Archive The tests of location in the value archives. Contains 7(8) tests of the value archiver to verify the correct functioning of the sequential packing mechanism. 1:arch Value archive 2:period Period of the values, microseconds 3:archtor Archiver 11) Base64Code Mime Base64 algorithm encoding tests. ===================== Subsystem "User interfaces" options =============== ------ Parameters of the section '/sub_UI/' of the configuration file ------ FontSnthHglCode <font> Font used in the code syntax highlight, by default "monospace". ======================= Module <UI:Vision> options ======================= ---- Parameters of the module section '/sub_UI/mod_Vision/' of the configuration file ---- StartUser <user> Start-up, no-password, user. UserPass <pass> User password for non-local start. RunPrjs <list> List of projects to be launched at the start of the module. ExitLstRunPrjCls <0|1> Exit closing the last completed project (by default 1). CachePgLife <hours> Lifetime of the pages in the cache (by default 1). CachePgSz <numb> Maximum number of the pages in the cache (by default 10). VCAstation <id> The station with the VCA engine ('.' Is local). RestoreTime <seconds> Connection recovery time. ======================= Module <UI:QTStarter> options ======================= --QtInNotMainThread Starts Qt into a different from the main thread. --showWin=<0,1,2> Window display mode, initial and which is allowed to change from: 0-typical window, 1-maximized window, 2-full screen. --simulRightMKeyTm Timeout, in seconds, to simulate the right mouse key and context menu at holding the left mouse key in the time - more to zero. ----------- Qt debug commandline options ---------- --noX11 Prevent the launch of Qt, preferably for a clean console. --sync Switch to Sync X11 for debugging. --widgetcount Print debug messages at output, the number of widgets left unselected and their maximum number. ----------- Qt commandline options ---------------- --qws Do this with Qt server software for embedded Linux. --style=<name> Sets the GUI style to <name> (windows, platinum, plastique, ...). --stylesheet=<path> Set the style sheet from the file by <path>. --session=<name> Restore from the previous session with the specified <name>. --reverse Set the layout in Qt::RightToLeft. --graphicssystem=<nm> Install rendering mechanism for screen widgets and QPixmaps (raster, opengl). --display=<nm> Set the X display (typically $DISPLAY). --geometry=<geom> Set the client geometry of the first display window. ---- Parameters of the module section '/sub_UI/mod_QTStarter/' of the configuration file ---- StartMod <moduls> List of the modules that are started, separated ';'. CloseToTray <0|1> Closing all windows or starting without Qt modules to the system tray. SessCntr [0...*3] Sessions control-restart: 0-if running, 1-anyway, 2-immediately, 3-never. Style <name> The GUI style of Qt. Font <font> Common Qt font. Palette <colors> Twenty colors of the palette separated by symbol ',' in three lines for active, disabled and inactive groups. StyleSheets <CSS> Rules of the Cascade Style Sheets. ======================= Module <UI:QTCfg> options ======================= ---- Parameters of the module section '/sub_UI/mod_QTCfg/' of the configuration file ---- StartPath <path> Initial page path of the configurator. StartUser <user> Starting user without password. ======================= Module <UI:WebVision> options ======================= ---- Parameters of the module section '/sub_UI/mod_WebVision/' of the configuration file ---- SessTimeLife <min> Lifetime of the sessions in minutes (by default, 10). SessLimit <numb> Maximum number of the sessions (by default 5). CachePgLife <hours> Lifetime of the pages in the cache (by default 1). CachePgSz <numb> Maximum number of the pages in the cache (by default 10). PNGCompLev <lev> Compression level [-1..9] of the creating PNG-images. ImgResize <0|1> Resizing raster images on the server side. =================== Subsystem "Modules scheduler" options ================= --modPath=<path> Directories with the modules, separated by ';', they can include a files' template at the end. ------ Parameters of the section '/sub_ModSched/' of the configuration file ------ ModPath <path> Directories with the modules, separated by ';', they can include a files' template at the end. This is a synonym of the system wide parameter "ModDir" ModAllow <list> List of the shared libraries allowed for the automatic loading, attaching and starting (bd_DBF.so;daq_JavaLikeCalc.so). Uses '*' value to allow all the modules. ModDeny <list> List of the shared libraries denied for the automatic loading, attaching and starting (bd_DBF.so;daq_JavaLikeCalc.so). ChkPer <seconds> Period of the checking for new shared libraries(modules), 0 to disable.
OpenSCADA is from the beginning a program that can be started from the console or terminal by typing openscada. In this way, the program will start with its action messages in this console and the console lock on the user actions waiting, which is the default startup mode in the console-terminal and can be used to operative debugging and control the result of actions and errors. In addition to the typical mode, there are also three other modes that are defined by the transmission of options to the startup command:
OpenSCADA is modular one and has modules for local graphical interfaces, and this can be launched in a graphical interface, which occurs simultaneously at the typical launch from the console, in the presence of an accessible X-server. To run exclusively in, and with a graphical interface, the command of the typical mode can, and is used by: the configuration of the shortcut icons-links of the desktop, the launch of programs (also automatic) from the environment of the graphical environment — the desktop (DE). The module of the local graphical environment launching can provide several modes itself, which can be found in the documentation for this module, which is currently UI.QTStarter and which provides the modes:
The simple startup is little useful, inconvenient and involves the use and operation of only one configuration, which is configuration file {sysconfdir}/oscada.xml as the primary configuration storage. To enable configuration choices, the command line parameter --config is provided at startup of the program and changing of the program working directory before launching or by parameter "WorkDir" this configuration file, which can be used and used exclusively by OpenSCADA to version 0.9 through the creation of a separate command line script (Shell) for a separate configuration. The OpenSCADA 0.9 version adds the concept of the "OpenSCADA Project", which was originally implemented by a separate command line script openscada_start, and then integrated into the OpenSCADA core and the startup module of the local graphical interface.
OpenSCADA 0.9 identified, implemented and finalized the essence of the OpenSCADA project as a separate site (folder) with the configuration and all data of a separate solution-project of the SCADA-system — a technological process object, a PLC, a visualization server, a Web server, and more.
The data of a single project-folder typically includes:
The project folder name is the project name and is located in the OpenSCADA work folder. The OpenSCADA work folder is divided into a system ("{datadir}/openscada", where "datadir" is usually "/usr/share"), which is read-only for the normal-unprivileged user, and an user ("{HOME}/.openscada"), which, if necessary, is created in the user's home directory. The predefined projects and OpenSCADA libraries that are installed by the corresponding Linux distribution packages are usually placed into the system work folder. Therefore, in order to ensure full operation, projects and libraries from the system work folder are copied to the user one, which the project manager carries out automatically.
The first mechanism for implementing the project's essence was the openscada_start command line scripts, which are still provided for compatibility, envisaging and defining the following features and requirements:
In order to unify and expand the functionality, and openscada_start exploitation experience, the essence of the project was later integrated into the OpenSCADA core and the module UI.QTStarter of the local graphical interfaces execution. Therefore, the OpenSCADA core, namely the primary openscada binary file, involves determining the configuration file, the data folder and the name by the specified project name and switching to that configuration in accordance with paragraphs 1, 2 and 4 above of the listed functions of the project manager. Creating the interface elements for selecting and creating new projects, item 5, implements the UI.QTStarter local graphical interface module (Fig.5a,5c). Items 3 and 6 are moved to a separate command line script openscada-proj because of the specificity of these operations to the software platform, and therefore the need for a simple adaptation to this specificity.
Therefore, OpenSCADA can now be run in both demon-service and GUI mode simply by specifying the name of the current project in four ways:
You can create a new project from the UI.QTStarter local graphical interface (Fig.5c) and through the command line script for the project manager openscada-proj, which is actually called from local graphical interface.
Result of the command openscada-proj --help execution ...
Projects management script of OpenSCADA mostly designed to call from OpenSCADA but also can be used independently. The script is mostly software platform specific and relates now for Linux. openscada-proj list openscada-proj proc|create|remove|update {ProjName} Commands: list - allowed projects list; proc - proceed for copy RO projects to WR, create desktop links, process core dumps; create - create new projects or copy RO projects to WR, create desktop links; remove - remove project; update - update from 0.8.0 LTS; Arguments: ProjName - project name; Environment variables: dPrj - directory of projects OpenSCADA, can be RO; dPrjUser - directory of projects OpenSCADA of the user, WR; dSysCfg - directory of system configuration; dData - directory of system data; openscada-proj backup|backupRestore {ProjName} [{BackupName}] openscada-proj backupList {ProjName} Commands: backup - backup the selected project <ProjName> to the name <BackupName>, or to the current date at missing; backupRestore - restore the selected project <ProjName> from the pointed backup name <BackupName>, or from the last one at missing; backupList - list the project <ProjName> backups. Arguments: ProjName - project name; BackupName - the backup archive name. Environment variables: OSCD_TAR_ComprPrg - TAR compression program, by default gzip; OSCD_TAR_Args - TAR extra arguments, by default \"--exclude=lock --exclude=ARCHIVES\"; OSCD_BackLim - Backups limit, by default 10.
In general, the command line script for the project manager openscada-proj includes such project functions and commands:
Additionally, the command line script contains the project backups manager commands:
Backup is generally done in the OpenSCADA working folder along with the folders of the projects themselves, for which packed folder files are created with the name {ProjName}_{BackupName}.backup, for example — "Boiler_2020-06-24_20.09.backup". By default, project folders are compressed with "gzip", which can be changed by setting the environment variable "OSCD_TAR_ComprPrg". The backup files limit is set by default to 10 and you may change that by the environment variable "OSCD_BackLim". You also can append some specific arguments to the TAR archiver by the environment variable "OSCD_TAR_Args", which by default set to "--exclude=lock --exclude=ARCHIVES" for excluding the file "lock" and folder "ARCHIVES" from the backup. The backup can be done from the outside, for example, from the established schedule with CRON, in addition to doing it manually from the graphical interface of the project manager (Fig.5a).
The OpenSCADA project organisation in a separate folder makes it easy to run ready-made projects in the service space — execution in the background, as well as further update and maintenance of this project without direct remote control. In fact, you can develop a project locally by keeping its folder in the user's work folder (typically "{HOME}/.openscada"), and to run in the service space just copy or package, transfer to a remote work device and unpack into the system work folder (default "/usr/share/openscada").
Service-background execution of programs in Linux is serviced by a suitably generated scripts, which are located in the folder "/etc/ini.d" and must be separate for each OpenSCADA project that runs in the service space. To simplify and eliminate the need to create your own scripts, OpenSCADA provides appropriate ones for standard cases-profiles that are typically supplied with the openscada-server and openscada-plc packages (openscada-lts-server and openscada-lts-plc for LTS).
Therefore, to launch the AGLKS library project in the service space, we:
# Connect from the superuser
su -
# ... for the live disk and some other Linux environments
sudo bash
# Stop down of execution of the previous server configuration and remove its folder
service openscada-server stop; rm -R /usr/share/openscada/server
# ... for LTS
service openscada-lts-server stop; rm -R /usr/share/openscada/server
# Copy the project "AGLKS" from the user home folder "{HOME}" also renaming to "server"
cp -R {HOME}/.openscada/AGLKS /usr/share/openscada/server
# Start the server already in the project "AGLKS"
service openscada-server start
# ... for LTS
service openscada-lts-server start
Note, that locally you may not to copy the entire project folder, but only make a symbolic link to it, but you get the risk of double project execution on a shared folder and data, which leads to the crash of one or both executions!
Difference between the project execution in the service-background environment from the user environment of the desktop is actually one, except for the lack of the local graphical interface of course, it is the absence of a locale in the background, ie the interface language will be English. And what can be fixed simply by changing or adding the configuration parameter <prm id="Lang">uk_UA.UTF-8</prm> to the section-tag "station" of the file oscada.xml of the background project.
Documents/Program_manual/en - GFDL | March 2024 | OpenSCADA 0.9.7 |